Xantrex Automatic Generator Manual do Utilizador Página 41

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 40
Installing the Auto Gen Start
975-0082-01-01 2–19
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.
Figure 2-11
Type 10 connection diagram
Table 2-11
Type 10 relay and timing preset configurations
Relay 1 mode
StartStop
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
15 s
Crank retry time
30 s
Shutdown bypass time
0 s
Start tries
3
18
17
START
16
14
13
12
GEN RUN SIGNAL
GROUND
STOP
Relay 1
Relay 2
5A fuse
5A fuse
AGS wiring harness Generator wires
Complete overcurrent protection
not shown. Refer to page 2–6.
Vista de página 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 123 124

Comentários a estes Manuais

Sem comentários